Your resource for expert Life Safety Code® and compliance insights.

Here you’ll find responses to readers' questions, interesting observations from the field, and more.

The world of healthcare compliance is constantly changing. Stay in the loop by subscribing to our free knowledge hub to get updates delivered right to your inbox.

Taylor Hatten Taylor Hatten

Replace Old Smoke Detectors?

Whether addressable or conventional, there’s no code that mandates the replacement of a smoke detector so long as it’s sensing smoke per the manufacturer’s listed sensitivity range.

Read More
Taylor Hatten Taylor Hatten

Fire Watch

If there are wet system sprinklers that protect below the suspended ceiling, plus dry system sprinklers located above in the attic space to protect above the drop ceiling, do I still need to conduct a fire-watch during construction?

Read More
Taylor Hatten Taylor Hatten

More on Power Strips

As I read NFPA 99-2012, section 10.2.3.6, power strips used within the patient care vicinity must only be used on movable equipment assemblies that are rack-mounted, table-mounted, pedestal-mounted, or cart-mounted.

Read More
Taylor Hatten Taylor Hatten

Power Strips

You cannot have only one type of power strip available for purchase and distribution throughout your healthcare facility.

Read More
Taylor Hatten Taylor Hatten

Eyewash Stations

While the ANSI standard Z358.1-2014 is the standard to follow for the installation, testing, and maintenance of an eyewash station, it is not the standard to follow to determine when an eyewash station is required.

Read More
Taylor Hatten Taylor Hatten

EPSS Circuit Breaker Test

For Level 1 Emergency Power Supply Systems, NFPA 110-2010, section 8.4.7 does require you to exercise the circuit breakers between the Emergency Power Supply (also called the generator) and the transfer switch load side on an annual basis.

Read More
Taylor Hatten Taylor Hatten

Evacuation Route Maps

CMS, NFPA, and the accreditation organizations do NOT require evacuation route maps.

Read More
Taylor Hatten Taylor Hatten

Storage Rooms

Section 19.3.2.1.5 (7) of the 2012 LSC says rooms or spaces that are larger than 50 square feet used for the storage of combustible supplies and equipment in quantities deemed hazardous by the AHJ are considered to be a hazardous area.

Read More
Taylor Hatten Taylor Hatten

Dietary Carts Left Unattended in Corridor

Food service carts would be used on floors of existing healthcare occupancies involving inpatients, where the corridors are required to be a minimum of 48 inches in clear width.

Read More
Taylor Hatten Taylor Hatten

Actual Alarm Count as a Fire Drill?

An actual alarm on the fire alarm system may count as a drill, but only if you evaluate the response of the staff, the building, and the fire alarm system.

Read More

Expert advice is just a few clicks away.