Sprinkler Obstructions

Q: My question is in regard to NFPA 13 sprinkler obstruction compliance…We want to install some surveillance monitors in our security office along a wall. How much vertical clear space is required between the monitors to the ceiling, if the monitors will be 30 inches away, horizontally from the sprinkler head?

A: Those monitors may extend vertically up to the ceiling as long as they are not directly underneath a sprinkler head, and they are attached to the wall. You said they were 30 inches away horizontally from the sprinklers, so you should be okay.

The Annex section A.8.6.6 of NFPA 13-2010 says the following:

“The 18 in. (457 mm) dimension is not intended to limit the height of shelving on a wall or shelving against a wall in accordance with 8.6.6, 8.7.6, 8.8.6, and Section 8.9. Where shelving is installed on a wall and is not directly below sprinklers, the shelves, including storage thereon, can extend above the level of a plane located 18 in. (457 mm) below ceiling sprinkler deflectors. Shelving, and any storage thereon, directly below the sprinklers cannot extend above a plane located 18 in. (457 mm) below the ceiling sprinkler deflectors.”

While the monitor may not be shelves, the concept is the same.

Brad Keyes
Brad Keyes, CHSP

Brad is a former advisor to Healthcare Facilities Accreditation Program (HFAP) and former Joint Commission LS surveyor. He guides clients through  organizational assessment; management training; ongoing coaching of task groups; and extensive one-on-one coaching of facility leaders. He analyzes and develops leadership effectiveness and efficiency in work processes, focusing on assessing an organization’s preparedness for a survey, evaluating processes in achieving preparedness, and guiding organizations toward compliance. 

As a presenter at national seminars, regional conferences, and audio conferences, Brad teaches the Keyes Life Safety Boot Camp series to various groups and organizations. He is the author or co-author of many HCPro books, including the best-selling  Analyzing the Hospital Life Safety Survey, now in its 3rd edition. Brad has also authored a variety of articles in numerous publications addressing features of life safety and fire protection, as well as white papers and articles on the Building Maintenance Program. Currently serving as the contributing editor of the monthly HCPro newsletter Healthcare Life Safety Compliance  gives Brad further insight into the industry’s trends and best practices.