Q: Is there a code from NFPA or Joint Commission in regards to “cloth” curtains hanging in around/in front of oxygen cylinders. And if so would it make a difference if it is in an office setting vs hospital setting?

A: Yes… Both NFPA and Joint Commission prohibits the storage of oxygen cylinders within 20 feet of combustibles (or within 5 feet of combustibles if the room is protected with sprinklers, see NFPA 99-2012, 11.3.2.3), when the quantity of compressed gas stored is equal to or exceeds 300 cubic feet. It does not make a difference where the stored compressed oxygen is stored. NFPA 99 applies to all healthcare facilities.

Brad Keyes
Brad Keyes, CHSP

Brad is a former advisor to Healthcare Facilities Accreditation Program (HFAP) and former Joint Commission LS surveyor. He guides clients through  organizational assessment; management training; ongoing coaching of task groups; and extensive one-on-one coaching of facility leaders. He analyzes and develops leadership effectiveness and efficiency in work processes, focusing on assessing an organization’s preparedness for a survey, evaluating processes in achieving preparedness, and guiding organizations toward compliance. 

As a presenter at national seminars, regional conferences, and audio conferences, Brad teaches the Keyes Life Safety Boot Camp series to various groups and organizations. He is the author or co-author of many HCPro books, including the best-selling  Analyzing the Hospital Life Safety Survey, now in its 3rd edition. Brad has also authored a variety of articles in numerous publications addressing features of life safety and fire protection, as well as white papers and articles on the Building Maintenance Program. Currently serving as the contributing editor of the monthly HCPro newsletter Healthcare Life Safety Compliance  gives Brad further insight into the industry’s trends and best practices.