Entries by BKeyes

Portable Fire Extinguishers

Q: In regards to portable fire extinguishers, I have a fully sprinkled building but my room that my hot water heaters are in are on the outside of the building. My furthest hot water room is more than 75 feet from the closet fire extinguisher. I looked in the Life Safety Code and have not more »

Medical Gas Alarm Panels

Q: Is it a requirement to keep access to the medical gas alarm panel clear in a similar manner that access to medical gas shutoff valves must remain clear? These alarm panels seem to always be mounted in a crowded area. A: I don’t think so. I do not see any language in NFPA 99-2012 more »

Hospital Grade Receptacles

Q: Do hospital grade receptacles need to be tested yearly in an ambulatory setting? A: Section 6.3.4.1 of NFPA 99-2012 says hospital-grade receptacle testing shall be performed after initial installation, replacement, or servicing of the device. It also says additional testing of receptacles in patient care rooms shall be performed at intervals defined by documented more »

Clinical Needs Locks

Q: For clinical needs locks, can occupants pass through four locked doors (patient room door, a cross-corridor door, another cross-corridor door, and a door at exit discharge) in a required single path of egress? (All options have 4 locked doors in the path.) A: The 2012 Life Safety Code does not address any restrictions on more »

Lower Bottom Rod Latching

Q: My question is regarding a 2-hour fire-rated wall that is separating our physical therapy department and the main hospital. In between the two is a long glass hallway with a dual egress 90-minute fire-rated door. The doors are top latching. I have had an environment of care consultant say that the door has to more »

Manual Shutdown Switch

Q: We got a hit on our life safety inspection because we were told the manual shutdown switch be detached from the generator. The deficiency report says “The manual shutdown switch should be located external to the waterproof enclosure of the generator and should be appropriately identified.” The manual shut off switches of our generators more »

Sprinkler Obstructions

Q: My question is in regard to NFPA 13 sprinkler obstruction compliance…We want to install some surveillance monitors in our security office along a wall. How much vertical clear space is required between the monitors to the ceiling, if the monitors will be 30 inches away, horizontally from the sprinkler head? A: Those monitors may more »

Annual Alarm Transmission Test

Q: Is the alarm transmission verification test generally performed by a fire alarm testing company on every device during an annual test/inspection? I also thought that this was a quarterly requirement. I would verify receipt and timing of transmission with the central station once a quarter during fire drills. Do I have this confused with more »