Entries by BKeyes

Fire Alarm Testing Qualifications

Q: I have a question regarding testing and repair of fire alarm system in a hospital setting. Is a maintenance person who is employed by the hospital as an electrician but who has 10-years of on-the-job training qualified to swap out a bad smoke detector or smashed fire pull station? Is he allowed to test the more »

Warning Placards Above Class K Extinguishers

Q: We recently were cited for not having the placard placed on the wall above the K Fire Extinguisher, however, the “warning” on the front of the extinguisher is in red and it states: “WARNING” “IN CASE OF APPLIANCE FIRE, FIRST, ACTIVATE FIRE SUPPRESSION SYSTEM OR TURN OFF APPLIANCE TO REMOVE HEAT SOURCE”. The instructions more »

Blanket Warmers

Q: Is there a code for blanket warmers, towel warmers and such equipment that is used in a medical setting? Since they have a heating element would it be the same as having a space heater? A: No… Portable space heaters are regulated by section 19.7.8 of the 2012 LSC. Blanket warmers are not regulated more »

Alcohol Storage

Q: A question for you about alcohol storage. If we have over 5 gallons of alcohol, 70% isopropyl rubbing alcohol in a 1-hour rated room, is that acceptable? A: It depends what type of containers the alcohol is stored in, the capacity of the containers, the size of the room, and the location of the more »

Sizing Fire Extinguishers

Q: I can find a lot of information about portable fire extinguishers but nowhere can I find what size is required for use in a hospital. Can you point me in the right direction? We specified 2.5 lbs. and 5 lbs. and no one can tell me what is correct. A: Section 9.7.4.1 of the more »

Is a Fire Watch Necessary?

Q: We have a complete gut renovation project that consist of two buildings (Admin. Bldg. & Lab Bldg.). The buildings are connected in all three levels and will be unoccupied. Both buildings are connected on the first level only to the adjacent occupied building. A one-hour barrier will be built to separate the occupied building more »

Air Pressure Requirements

Q: This question concerns isolation room negative pressure parameters. Our ICU isolation rooms have two sensors for air pressure; one located inside the room and the other located outside the room, of course. Could you tell me what the maximum and minimum negative pressure standard is supposed to be? Is there even such a standard? more »