May 30 2018

Generator Testing

Category: BlogBKeyes @ 12:00 am
Share

Q: Does our hospital have to test the generator for 30 minutes every week, and then 1-hour once a month? We have programmed our generators to operate every Wednesday at 12 noon and run for 30 minutes. We do ATS test once a month and record information when running.

A: According to section 9.1.3.1 of the 2012 Life Safety Code, emergency power generators must be tested in accordance with NFPA 110. Section 8.1.1 of NFPA 110-2010 says the routine testing of the emergency power generators must be based on all of the following:

  • Manufacturer’s recommendations
  • Instruction manuals
  • The requirements of NFPA 110
  • The AHJ’s requirements

While NFPA 110 does not have any requirements to operate the generator on a weekly basis, there may be manufacturer requirements or AHJ requirements that do. Section 8.4.1 of NFPA 110-2010 specifically says generators must be inspected weekly but operated under load on a monthly basis. Section 8.4.2 requires the monthly load test to operate for 30 minutes. I suggest you check with your generator manufacturer and your state and local AHJs to see if they have specific weekly run-tests of the generator.

Tags: ,


May 16 2018

Generator Fuel Testing

Category: BlogBKeyes @ 12:00 am
Share

Q: What are the guidelines on the diesel fuel test for the generator as far as having it treated or a sample sent off for testing?

A: The new 2012 Life Safety Code references the 2010 edition of NFPA 110, the standard for emergency and standby power systems. Section 8.3.8 of the NFPA 110-2010 requires the fuel for the generators to be tested annually for quality. According to more recent editions of NFPA 110, this test is to be conducted in accordance with ASTM D975, Standard Specification for Diesel Fuel Oils. You may purchase a copy of the standard direct for the ASTM website https://www.astm.org/Standards/D975.htm

Tags: ,


Jan 19 2018

Generator Testing

Category: BlogBKeyes @ 12:00 am
Share

Q: We have a generator that doesn’t meet the 30% load for the monthly run so we have to do an annual run with the load at 50% for 30 min and 75% for 60 min for a 90-minute continuous run. Our contractor did the annual run but he ran it with 52 % for 30 min , 75% for 30 min and 81% for 30 min, then he continued to run it for 2½ more hours dropping the percentages as he went for 4 continuous hours at not less than 30%. My question is does these meet the intent of the standards for both an annual and a 3-year load test?

A: Yes… I would say the test as you described meets both the annual requirements and the 3-year test requirements. The generator load testing requirements are minimum load settings, and it is permitted to exceed these minimums.

Tags: ,