Suite Entrance Doors

Q: A hospital has 2 different suites with double egress entry doors and the Joint Commission surveyor noted that these doors are supposed to have latching hardware because they are “corridor doors,” but in my experience, cross-corridor doors are not typically required to have latching hardware.  Can you weigh in on this?

A: I agree totally with the surveyor. According to the LSC, suites are nothing more than rooms; albeit a large room with smaller rooms inside. Therefore, corridor entrance doors to suites must positively latch because corridor doors are required to latch according to 18/19.3.6.3.5, 2012 LSC.

The thing that throws people off is what looks like a corridor inside a suite is not a corridor; it is a communicating space. The requirements of a corridor do not apply inside a suite. But the designers often make this space 8 feet wide and for all intent and purposes people think it is a corridor. Then, the designer places double egress doors as entrances to the suite (which is good when you’re pushing patients in an out on beds) and the doors look like cross-corridor doors. They’re not; they are corridor doors.

The hospital has to make those doors positively latch or they have to change the designation from a suite to a corridor, which is not advisable.