Stairwell Signage

In Case of Fire Web 2If you were a bit surprised by the wording of the sign to the left… You’re not alone. I had to do a double-take when I first saw it, as it certainly got my attention.

The sign is a marketing strategy by the Stairwell Signage Solutions company in Palm Beach Gardens, Florida, and is re-printed here with permission. The sign is an ominous warning to facility managers that their existing stairwell signage may not be compliant with the new 2012 Life Safety Code.

When the new 2012 LSC is adopted facilities will have to comply with the following requirements, found in section 7.2.2.5.4:

 

  • New enclosed stairwells serving three or more stories and existing enclosed stairwells serving five or more stories must have stairwell identification signs (previously, the 2000 LSC only required stairwells serving five or more stories to have stairwell identification signs);
  • The stairwell must be provided with identification signs inside the enclosure at each floor landing;
  • The signage must indicate the floor level;
  • The signage must indicate the terminus of the top and the bottom of the stairwell;
  • The signage must indicate the stairwell name (identification);
  • The signage must indicate the floor level of, and the direction to, the exit discharge;
  • The signage must be located inside the enclosure approximately 60 inches above the floor landing in a position that is visible when the door is open or closed;
  • The signage must be continuously illuminated with emergency power back-up capability (this was not previously required);
  • The floor level designation must be tactile in accordance with ICC/ANSI A117.1 (this was not previously required);
  • The signage must be painted or stenciled on the wall or on a separate sign securely attached to the wall (this was not previously required);
  • The name of the stairwell must be located at the top of the sign in minimum 1 inch tall lettering (this was not previously required);
  • Stairwells that do not provide roof access must read ‘NO ROOF ACCESS’ underneath the name of the stairwell in 1 inch tall lettering (this was not previously required);
  • The floor level number must be located in the middle of the sign in 5 inch tall numbers (this was not previously required);
  • The identification of the lower and upper terminus of the stairwell must be located at the bottom of the sign in 1 inch tall lettering (this was not previously required).

The phrase ‘this was not previously required’ is referring to the 2000 LSC. If you would like to contact Stairwell Signage Solutions, contact Stephen Salzberg, at imagemaven@aol.com.