Apr 20 2015

Soiled Utility Room Door Signage

Category: Doors,Questions and Answers,Signs,Soiled Utility RoomsBKeyes @ 6:00 am
Share

Q: Are you aware of any door signage requirements for soiled utility rooms and/or trash rooms?

A: There is no Life Safety Code requirement for signs on a soiled utility room door or a trash collection room door, unless the door could somehow be confused with an exit door. Then a ‘NO EXIT’ sign will have to be posted on the door, with the word ‘NO’ 2 inches tall, and the word ‘EXIT’ 1 inch tall, and the word ‘NO’ has to be on top of the word ‘EXIT’. If the doors to the soiled utility room or the trash collection room are fire-rated doors, then the sign must be no larger than 5% of the overall surface area of the door, and can only be attached to the door with adhesives. Nails and screws are not permitted to attach a sign to a fire rated door. Perhaps you may be thinking of a state regulation whereby every door must have a number or name assigned to it. I have seen this regulation in many states. However, I am not aware of any CMS, Joint Commission, HFAP or DNV requirement for signs on these doors.