Fire Rated Barriers vs. Smoke Barriers

Q: Are doors in fire rated barriers also required to be listed and installed as a smoke barrier?

A: No… Fire rated barriers are not necessarily smoke barriers. They are two distinctly different barriers with different purposes. Now, if an organization wanted to combine the two purposes into one barrier, then that is acceptable as long as you meet the most restrictive requirements of each type of barrier. A fire-rated barrier requires fire-rated opening protectives (i.e. doors, windows). Fire rated door assemblies are required to have fire-rated doors and frames, self-closing devices, and positive latching. A fire rated barrier that is rated at 2-hours or greater must have fire dampers in any HVAC ductwork that penetrates that barrier.

A new construction smoke barrier is required to have walls constructed to 1-hour rating, but the doors and frames in the smoke barrier are not required to fire-rated. The doors are only required to be 1¾ inch thick, solid bonded, wood-core doors, or be of construction that resists fire for 20 minutes. Please understand that this does not mean the door has to be 20 minute rated; only be of construction that resists fire for 20 minutes. The door has to be self-closing but is not required to be positive latching. HVAC ductwork penetrating a smoke barrier must have smoke dampers, unless both sides of the smoke compartment barrier are protected with sprinklers. However, please understand this is an NFPA exception and the IBC does not recognize that, so your state or local authorities may not allow a smoke barrier without smoke dampers in the HVAC ductwork.

So, technically, a combination fire-rated barrier and a smoke barrier could be the same wall, but the requirements for both barriers need to be included.