Electrical Panels

imagesCATTF4OXThere are quite of few issues concerning electrical panels that need to be addressed during a survey. Hospitals frequently take electrical panels for granted and overlook some of the more obvious requirements. Surveyors are better educated and prepared to evaluate your electrical panels during the survey.

Access to electrical panels must not be obstructed. There must be at least 36 inches clearance in front of the electrical panels and at least 30 inches clearance to one side of the electrical panel. The width of the electrical panel is included in the 30 inch side clearance.

While there are no direct standards that say the electrical panels must be locked, the risk of unauthorized access by unscrupulous individuals who could turn off circuit breakers controlling vital functions is a risk that must be addressed. In other words; access to the electrical panels should be secure, unless the healthcare organization has conducted a risk assessment that addresses the risk of unauthorized access. An example where a risk assessment may indicate an unlocked electrical panel is acceptable is where the circuit breakers in the panel do not serve a vital function of safety.

Circuit breakers are required to be labeled as to the circuits that they serve, or are required to be labeled as “Spares”. In older healthcare facilities this may be a problem since renovations may change what is served by the circuits and the breaker schedule may not be up to date. A breaker turned “Off” because it is a spare still needs to be labeled as such.